The Use of Risk-Based Frameworks for Estimating Unintended Emissions: A Case Study on Flaring
Tap a block to jump to that section, or scroll down to begin at Overview of Case Study.
1 Center for Energy and Environmental Systems Analyses (CEESA), The University of Texas at Austin · 2 Artie McFerrin Department of Chemical Engineering, Texas A&M University
Applying a reliability-based framework requires first defining a specific system boundary and flare configuration. This section expands on these, including a more detailed process description for the process flow diagram shown in the poster, and some additional details on the site and flare configuration.
The Case Study
An elevated, air-assisted, low pressure flare at a tank battery site in the Permian Basin, Texas, servicing five wells 6 to 24 months after first production. The facility for this case study is hypothetical, built to be representative of similar sites in the region rather than any single real one. The system boundary, equipment, and operating parameters are informed by a combination of the following: TCEQ Air Permits for tank batteries in the region, flare design literature (API 512 and 537), and engineering judgment.
Site Process Flow Diagram and Description
Scroll to walk through the diagram, or keep scrolling past it to move on.
Flare Configuration
Scroll to walk through the flare itself, or keep scrolling past it to move on.
To estimate the daily volume of gas to the low pressure flare and the vapor compositions of the water and oil tanks, the Emission Composition Tool was utilized. This tool performs a query on a large database to identify the closest matching condensate and water tank flash composition given a set of inputs. Refer to "Beyond the Poster" for the tool inputs.
| Species | Water Tank Flash [MSCF/day] | Oil/Cond Tank Flash [MSCF/day] |
|---|---|---|
| Methane | 5.42 | 10.5 |
| Ethane | 1.24 | 19.2 |
| Propane | 0.447 | 35.5 |
| Isobutane | 0.147 | 18.6 |
| n-Butane | 0.116 | 38.2 |
| Isopentane | 0.0251 | 5.36 |
| n-Pentane | 0.0242 | 5.39 |
| n-Hexane | 0.0344 | 4.53 |
| C7+ | 0 | 0 |
| Sum | 7.45 | 137.3 |
Beyond the poster
| Composition Profile ID | Composition_CaseStudy |
|---|---|
| Composition Data Source | thermodynamics |
| Condensate (or OIL) formation | yes |
| Number of Separator Stages | 2 |
| API Gravity | 41.795 |
| Gas to Oil Ratio [scf/bbl] | 2000 |
| Temperature [F] | 120 |
| 1st Stage Pressure [psia] | 89.7 |
| 2nd Stage Pressure [psia] | 59.7 |
| Methane [molar fraction] | 0.72931 |
| Ethane [molar fraction] | 0.13838 |
| Propane [molar fraction] | 0.06831 |
The value chosen for the API Gravity field was the average of the Oil API Gravity for Stock Tanks provided in TCEQ Air Permits for six tank battery sites in the Texas Permian Basin. The values for the methane, ethane, and propane molar fractions were average produced gas molar compositions derived from public gas composition data for two counties in the region.
Definition of the Top Event
The top event is defined as the escape of uncombusted methane emissions from the flare due to the flare destruction removal efficiency dropping below 98%. This includes instances where vent gas is released because the flare flame is unlit.
Fault Tree and Failure Mechanisms
Hazard identification (HazID) and hazard and operability (HazOp) analysis using guide words was used to systematically identify hazards the flare was susceptible to for the top event to occur. This led to the development of the fault tree for this case study, shown below.
Tap a pathway below to expand its description. Tap it again to collapse.
Pathway A: High Vent Gas Flow
High Vent Gas Flow refers to the phenomenon of the vent gas to the flare tip being too high, leading to inadequate mixing in the combustion envelope of the flame and methane escaping. This is caused by either separator dump valve diaphragm rupture, or separator dump valve seat failure.
Separator Dump Valve Diaphragm Rupture and Separator Dump Valve Seat Failure are two failure mechanisms considered in this case study. The dump valve of the separator is responsible for controlling the level of liquids in the vessel by allowing fluids to exit the separator at set levels. The dump valve diaphragm can develop holes over time due to erosion from abrasive solid particles in the fluid, such as sand, that passes through the valve. This can cause the dump valve to fail open, which can lead to continuous fluid dumping, and potential gas blow-by into the water and oil storage tanks. The valve seat is made of ceramic and similarly wears out due to sand in the fluids, which also causes the dump valve to fail open.
Refer to the "Beyond the Poster" section below to see the cross section of a weight operated dump valve.
Pathway B: Liquid Carryover
Liquid Carryover refers to the unintended entrainment of hydrocarbon condensates in the vent gas stream. The failure mechanism for this is a high-high level switch failure for the knockout pot. When this switch fails, accumulated liquids are not pumped out, and enter the vent gas line.
Pathway C: Low NHV in Combustion Zone
This pathway is still being refined and any feedback is appreciated.
Low NHV in Combustion Zone (<270 BTU/SCF) is caused by two intermediate pathways. Over-Assist or Low Vent Gas NHV (<300 BTU/SCF).
- Over-Assist: occurs when there is simultaneously Low Vent Gas Flow to the flare tip, and Over-Aeration in the combustion zone of the flame. This is because, assuming that the air-assist control system is operating properly, the flare is designed to operate at low vent gas flow. However, if more air than necessary is introduced to the combustion zone of the low vent gas flow, the air-to-fuel ratio will become too high in pockets of the flame for proper combustion.
- Low Vent Gas Flow is caused by the flame arrestor fouling, debris buildup in the vent line, or liquid/condensate holdup in the vent line.
- Over-Aeration is caused by either the blower motor being manually set to high, or high wind conditions.
- Low Vent Gas NHV refers to when the heating value of the gas drops below the required 300 BTU/SCF in the EPA 30 CFR 60.18. This is caused by the thief hatch being left open during gauging, the thief hatch not sealing properly, or a perforation in the tank. These each lead to air ingress into the tanks which dilutes the tanks vapors and lowers the vent gas NHV.
Pathway D: Unlit Pilot
The Unlit Pilot pathway is complicated and has its own dedicated fault tree analysis, performed by group member Siddhartha Rayasam.
Pathway E: Flare Tip Damage
Flare Tip Damage refers to when mechanical damage to the flare tip contributes to poor mixing in the combustion envelope of the flame, leading to escaped methane emissions. This pathway is caused by Wear and Tear, VFD Panel Failure, or Vacuum Conditions in Tanks.
Wear and Tear is the failure of the flare tip over time, derived from an average vendor-provided lifetime.
VFD Panel Failure is the failure of the control panel for the VFD for the blower motor over time. When this happens, the blower motor stops receiving power, and due to the lack of sweep gas, the flame will sit on the flare tip and wear it out faster.
Vacuum Conditions in Tanks occurs during water hauling or oil unloading events during loss of transfer capacity, as well as when tank bottoms are pulled. When the truck transfer rates are high enough, there can be slight vacuum conditions in the tank. These vacuum conditions cause the flare flame to be pulled closer to the flare tip and wear it out faster.
Beyond the poster
Determining the minimal cut set
Before any calculations are performed, the minimal cut set is determined. Our Fault Tree Analysis Tool performs this.
Event probability
Next, for each event, P, the event probability, is calculated. P is the likelihood that an event occurs or exists in a failed state within a specified mission time (1 year). It is dimensionless, and between 0 and 1.
There are several different parameter forms used to calculate P for the basic events. Each require different inputs. Three main ones were used for this fault tree analysis:
1. Failure rate with repair rate. Used for equipment that fails and gets fixed. Inputs are the failure rate, λ, and the Mean Time To Repair (MTTR).
λ: failure rate, [failures/time] μ: 1/MTTR, [time-1]
2. Frequency with duration. Used for conditions/states that come and go.
f: frequency, [events/time] d: mean duration, [time]
3. Fixed probability. For states or conditions whose probability is already known as a number, rather than derived from a running failure rate.
The basic event probabilities are then used to calculate intermediate event probabilities with Boolean Algebra.
| Event | λ, Failure Rate | MTTR, Mean Time To Repair | P, Probability |
|---|---|---|---|
| Separator Dump Valve Diaphragm Rupture | 1.83E-06/hr source: OREDA | 12 hours source: Assumption | 2.20E-05 |
| Separator Dump Valve Seat Failure | 1.83E-06/hr source: OREDA | 12 hours source: Assumption | 2.20E-05 |
| Liquid Carryover: Knockout Pot High-High Level Switch Failure | 1.27E-05/hr source: OREDA | 17 hours source: OREDA | 2.16E-04 |
| Flame Arrestor Fouling | 0.167/month source: Engineering judgment | 24 hours source: Assumption | 5.52E-03 |
| Debris Buildup in Vent Line | 1/year source: Engineering judgment | 24 hours source: Assumption | 2.77E-03 |
| Liquid/Condensate Holdup | 1/year source: Engineering judgment | 24 hours source: Assumption | 2.77E-03 |
| Thief Hatch Not Sealed Properly | 7.70E-06/hr source: OREDA | 24 hours source: Engineering judgment | 1.85E-04 |
| Tank Perforation | 1.34E-05/hr source: OREDA | 36 hours source: OREDA | 4.83E-04 |
| Wear and Tear | 0.1/year source: Engineering judgment | 3 months source: Assumption | 2.44E-02 |
| VFD Panel Failure | 0.2/year source: Engineering judgment | 24 hours source: Assumption | 5.55E-04 |
| Event | Frequency | Duration | P, Probability |
|---|---|---|---|
| Blower Motor Manually Set To High | 0.001/year source: Assumed human error rate | 1 week source: Assumption | 1.44E-01 |
| High Wind | 0.562/year source: Outdated manual calculation, placeholder | 2 hours source: Placeholder | 1.30E-04 |
| Thief Hatch Left Open | 0.001/year source: Assumed human error rate | 12 hours source: Engineering judgment | 1.19E-02 |
| Vacuum Conditions in Tanks | 4/year source: Engineering judgment | 24 hours source: Engineering judgment | 1.10E-02 |
| Event | Fixed Probability |
|---|---|
| Unlit Pilot | P = 0.056 (based on Fault Tree Analysis for Unlit Pilot scenario) |
| Fault Tree Main Branch | Estimated Probability (Highest to Lowest) |
|---|---|
| Unlit Pilot | 5.60E-02 |
| Flare Tip Damage | 3.60E-02 |
| Low NHV in Combustion Zone (<270 BTU/SCF) | 1.40E-02 |
| Liquid Carryover: Knockout Pot High-High Level Switch Failure | 2.20E-04 |
| High Vent Gas Flow | 4.40E-05 |
Dominant Contributors to Top Event
Beyond the poster
For failure rate data sourced from OREDA, engineering judgement must be used to pick components and failure modes that most closely match reality. For example, there is no "High-High Level Switch" in the OREDA handbook, so instead, a regular "Level" switch was chosen. The closest failure mode was "Fail to function on demand."
Where this goes
First, this fault tree and its calculations will be refined using feedback. Sensitivity analysis will explore how input values based on engineering judgment affect the results. Next, a fault tree will be constructed for the high pressure flare for this site, with threats and results compared with those for the low pressure, air assisted flare.
Open questions
- Do the assumptions for durations and mean time to repairs sound reasonable?
- How to most accurately capture the causes of Low NHV in Combustion Zone?
- Are the OREDA values chosen most representative of the understood failure mechanisms?